NA2XR(AL)Y 1 x (25-800) mm² 0.6/1 kV

Al / XLPE / AWA / PVC
(Aluminium Conductor, XLPE Insulated, Aluminium Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.


Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen

Note :
Conductor Shape
25 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 800 sqmm supplied in non compacted circular stranded (rm) or compacted circular stranded (cm) conductor shape

Standard Packing
25 - 500 sqmm supplied in wooden drum @ 1000 m
630 - 800 sqmm supplied wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25
16.6 344
35
17.8 403
50
19.5 486
70
22.0 591
95
23.5 699
120
25.5 830
150
28.0 994
185
30.0 1,160
240
33.5 1,428
300
36.0 1,678
400
42.5 2,365
500 45.5 2,704
630 50.0 3,272
800 56.5 4,175

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
Trefoil formation
Flat formation
in air in ground in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) (mH/km) Max. (A) Max. (A) Max. (A) Max. (A) Max. (kA)
25
1.20 1.539 0.379 0.426 123 120 126 123 2.35
35
0.868 1.113 0.360 0.406 149 143 153 147 3.29
50
0.641 0.822 0.343 0.389 181 169 186 174 4.70
70
0.443 0.568 0.326 0.372 228 207 234 213 6.58
95
0.320 0.411 0.313 0.359 278 247 285 253 8.93
120
0.253 0.325 0.310 0.356 323 281 331 287 11.28
150
0.206 0.265 0.302 0.348 371 315 380 321 14.10
185
0.164 0.211 0.296 0.342 427 356 436 361 17.39
240
0.125 0.162 0.287 0.333 507 410 516 416 22.56
300
0.100 0.130 0.282 0.328 580 460 589 464 28.20
400
0.0778 0.102 0.279 0.325 683 519 687 518 37.60
500 0.0605 0.080 0.276 0.322 775 580 775 574 47.00
630 0.0469 0.064 0.271 0.317 885 645 877 633 59.22
800 0.0367 0.052 0.273 0.319 980 693 961 672 75.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information