N2XKR(AL)Y 1 x (16-800) mm² 0.6/1 kV

Cu / XLPE / LS / PVC / AWA / PVC
(Copper Conductor, XLPE Insulated, Lead Sheathed, Aluminium Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where that is a
risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation and operation.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 800 sqmm supplied in non compacted circular stranded (rm) or compacted circular stranded (cm) conductor shape

Standard Packing
16 - 185 sqmm supplied in wooden drum @ 1000 m
240 - 800 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
16
23.0 1,199
25
23.0 1,265
35
23.0 1,342
50
24.0 1,514
70
26.5 1,873
95
28.0 2,220
120
30.0 2,648
150
32.0 3,047
185
35.0 3,703
240
39.0 4,681
300
42.0 5,447
400
46.5 6,729
500 52.0 8,458
630 57.5 10,580
800 63.0 12,944

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
Trefoil formation
Flat formation
in air in ground in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) (mH/km) Max. (A) Max. (A) Max. (A) Max. (A) Max. (kA)
16
1.15 1.466 0.489 0.535 127 119 130 121 2.29
25
0.727 0.927 0.440 0.486 167 154 171 158 3.58
35
0.524 0.668 0.410 0.456 202 185 207 189 5.01
50
0.387 0.494 0.381 0.427 245 220 251 225 7.15
70
0.268 0.342 0.366 0.413 306 268 313 273 10.01
95
0.193 0.247 0.349 0.396 372 319 379 324 13.59
120
0.153 0.196 0.340 0.386 428 361 436 366 17.16
150
0.124 0.159 0.334 0.380 485 401 493 406 21.45
185
0.0991 0.128 0.327 0.373 555 449 562 452 26.46
240
0.0754 0.098 0.321 0.367 649 509 651 507 34.32
300
0.0601 0.079 0.314 0.360 731 562 729 557 42.90
400
0.0470 0.063 0.309 0.355 826 621 818 610 57.20
500 0.0366 0.050 0.308 0.354 920 669 902 650 71.50
630 0.0283 0.041 0.301 0.347 1023 724 997 698 90.09
800 0.0221 0.034 0.296 0.342 1118 773 1085 742 114.40

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information