N2XKB(AL)Y 1 x (16-800) mm² 0.6/1 kV

Cu / XLPE / LS / PVC / DATA / PVC
(Copper Conductor, XLPE Insulated, Lead Sheathed, Double Aluminium Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For indoors, outdoors, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and low mechanical damage may
occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 800 sqmm supplied in non compacted circular stranded (rm) or compacted circular stranded (cm) conductor shape

Standard Packing
16 - 185 sqmm supplied in wooden drum @ 1000 m
240 - 800 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
16
22.0 1,140
25
22.0 1,205
35
22.0 1,279
50
23.0 1,452
70
24.5 1,766
95
26.5 2,107
120
28.5 2,522
150
30.5 2,900
185
33.5 3,540
240
36.5 4,416
300
39.5 5,160
400
43.5 6,406
500 48.0 7,941
630 53.5 9,999
800 59.5 12,304

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
Trefoil formation
Flat formation
in air in ground in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) (mH/km) Max. (A) Max. (A) Max. (A) Max. (A) Max. (kA)
16
1.15 1.466 0.479 0.526 126 118 128 121 2.29
25
0.727 0.927 0.431 0.477 165 153 169 157 3.58
35
0.524 0.668 0.400 0.447 199 184 204 189 5.01
50
0.387 0.494 0.372 0.418 241 219 247 224 7.15
70
0.268 0.342 0.354 0.400 301 267 308 273 10.01
95
0.193 0.247 0.338 0.384 366 319 375 325 13.59
120
0.153 0.196 0.329 0.375 424 361 433 368 17.16
150
0.124 0.159 0.322 0.369 481 404 491 410 21.45
185
0.0991 0.128 0.316 0.363 553 454 563 459 26.46
240
0.0754 0.098 0.307 0.354 652 521 661 525 34.32
300
0.0601 0.079 0.301 0.347 742 581 748 582 42.90
400
0.0470 0.063 0.298 0.344 848 648 849 645 57.20
500 0.0366 0.051 0.292 0.338 965 719 959 708 71.50
630 0.0283 0.041 0.286 0.333 1088 789 1071 769 90.09
800 0.0221 0.034 0.283 0.329 1203 852 1172 821 114.40

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information