NA2XSEKY 3 x (25-300) mm² 3.6/6 kV

Al / XLPE / CTS / PVC / LS / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 35 sqmm supplied in wooden drum @ 1000 m
50 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 39.5 3,292
35 43.0 3,824
50 46.0 4,419
70 50.5 5,264
95 54.5 6,172
120 58.5 7,089
150 62.0 7,938
185 66.0 9,076
240 72.0 10,662
300 78.5 12,746

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.346 118 113 2.35 1.03
35 0.868 1.113 0.326 143 135 3.29 1.03
50 0.641 0.822 0.314 170 159 4.70 1.03
70 0.443 0.568 0.296 213 195 6.58 1.03
95 0.320 0.411 0.284 258 233 8.93 1.03
120 0.253 0.325 0.276 297 264 11.28 1.03
150 0.206 0.265 0.269 336 295 14.10 1.03
185 0.164 0.212 0.262 386 335 17.39 1.03
240 0.125 0.162 0.256 453 387 22.56 1.37
300 0.100 0.130 0.253 516 434 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information