NA2XSEKFGbY 3 x (25-300) mm² 3.6/6 kV

Al / XLPE / CTS / PVC / LS / PVC / SFWA / PVC
(Aluminium Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol.
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 44.0 4,355
35 47.0 4,989
50 50.0 5,665
70 55.0 6,657
95 59.0 7,659
120 63.0 8,717
150 66.5 9,683
185 71.5 11,012
240 77.5 12,805
300 84.5 15,114

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 1.20 1.539 0.346 118 112 2.35 1.03
35 0.868 1.113 0.326 143 134 3.29 1.03
50 0.641 0.822 0.314 170 157 4.70 1.03
70 0.443 0.568 0.296 212 193 6.58 1.03
95 0.320 0.411 0.284 257 230 8.93 1.03
120 0.253 0.325 0.276 294 260 11.28 1.03
150 0.206 0.265 0.269 332 291 14.10 1.03
185 0.164 0.212 0.262 379 328 17.39 1.03
240 0.125 0.162 0.256 443 377 22.56 1.37
300 0.100 0.130 0.253 501 422 28.20 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information