N2XSEFGbY 3 x (25-300) mm² 3.6/6 kV

Cu / XLPE / CTS / PVC / SFWA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.

Special Features on Request :
• Oil Resistance
• Fire Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 38.5 2,603
35 41.5 3,074
50 44.5 3,641
70 48.5 4,536
95 52.0 5,542
120 56.0 6,516
150 59.5 7,593
185 63.0 8,940
240 69.0 11,074
300 75.5 13,395

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.342 152 147 3.58 1.03
35 0.524 0.668 0.325 185 175 5.01 1.03
50 0.387 0.494 0.313 219 205 7.15 1.03
70 0.268 0.342 0.296 273 251 10.01 1.03
95 0.193 0.247 0.285 330 299 13.59 1.03
120 0.153 0.196 0.276 379 339 17.16 1.03
150 0.124 0.160 0.268 430 379 21.45 1.03
185 0.0991 0.128 0.262 490 427 26.46 1.03
240 0.0754 0.099 0.255 573 490 34.32 1.37
300 0.0601 0.080 0.252 649 547 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information