N2XSERY 3 x (25-300) mm² 3.6/6 kV

Cu / XLPE / CTS / PVC / SWA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.

Special Features on Request :
• Oil Resistance
• Fire Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 35 sqmm supplied in wooden drum @ 1000 m
50 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 41.0 3,102
35 43.5 3,587
50 48.0 4,576
70 52.0 5,579
95 55.5 6,642
120 59.5 7,711
150 63.0 8,859
185 67.0 10,280
240 73.0 12,529
300 81.0 15,860

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.342 155 148 3.58 1.03
35 0.524 0.668 0.325 188 176 5.01 1.03
50 0.387 0.494 0.313 224 207 7.15 1.03
70 0.268 0.342 0.296 279 253 10.01 1.03
95 0.193 0.247 0.285 337 302 13.59 1.03
120 0.153 0.196 0.276 386 342 17.16 1.03
150 0.124 0.160 0.268 438 382 21.45 1.03
185 0.0991 0.128 0.262 499 430 26.46 1.03
240 0.0754 0.099 0.255 584 495 34.32 1.37
300 0.0601 0.080 0.252 662 552 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information