N2XSEY 3 x (25-300) mm² 3.6/6 kV

Cu / XLPE / CTS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.

Special Features on Request :
• Oil Resistance
• Fire Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 70 sqmm supplied in wooden drum @ 1000 m
95 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 37.0 1,868
35 39.5 2,275
50 42.5 2,778
70 46.5 3,577
95 50.0 4,517
120 54.0 5,422
150 57.5 6,406
185 61.5 7,662
240 67.5 9,664
300 74.0 11,852

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.342 149 145 3.58 1.03
35 0.524 0.668 0.325 181 173 5.01 1.03
50 0.387 0.494 0.313 215 204 7.15 1.03
70 0.268 0.342 0.296 268 249 10.01 1.03
95 0.193 0.247 0.285 325 297 13.59 1.03
120 0.153 0.196 0.276 374 337 17.16 1.03
150 0.124 0.160 0.268 425 378 21.45 1.03
185 0.0991 0.128 0.262 486 426 26.46 1.03
240 0.0754 0.099 0.255 570 492 34.32 1.37
300 0.0601 0.080 0.252 648 551 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information