NYFGbY 2 x (1.5-300) mm² 0.6/1 kV

Cu / PVC / SFWA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-1

Application

For installation in the ground, indoors, cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
1.5 - 95 sqmm supplied in wooden drum @ 1000 m
120 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
1.5 17.9 611
2.5 18.0 630
4 17.8 648
6 18.1 687
10 20.5 881
16 22.5 1,085
25 25.5 1,428
35 27.5 1,753
50 31.0 2,120
70 35.0 2,716
95 39.5 3,528
120 43.0 4,177
150 47.0 5,012
185 52.0 6,116
240 58.0 7,695
300 64.0 9,384

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 70°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
1.5 12.1 14.478 0.351 24 27 0.17
2.5 7.41 8.866 0.315 32 36 0.29
4 4.61 5.516 0.303 42 48 0.46
6 3.08 3.685 0.288 53 61 0.69
10 1.83 2.190 0.269 73 81 1.15
16 1.15 1.376 0.255 96 106 1.84
25 0.727 0.870 0.255 126 136 2.88
35 0.524 0.627 0.246 155 164 4.03
50 0.387 0.464 0.247 186 194 5.75
70 0.268 0.321 0.238 235 239 8.05
95 0.193 0.232 0.238 286 284 10.93
120 0.153 0.184 0.233 331 324 13.80
150 0.124 0.150 0.233 377 364 17.25
185 0.0991 0.121 0.233 430 408 21.28
240 0.0754 0.093 0.232 507 472 27.60
300 0.0601 0.075 0.231 577 530 34.50

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information